IP Conflict issue on HTPC Carousel Network

Saurav Das

Last Update 2 years ago

When any device with its default IP : 192.168.1.1 is connected in the network other than Main PLC. 

Symptoms: PLC IP is pinging from MIS PC, but data on portal are not changing. Portal is hanging. All values will be 'Loading...' on portal restart. 

Reason: Portal is not able to communicate with PLC because of IP Confliction.

Resolution 1: Disconnect the Router Device from network.

Resolution 2: Change the default IP of router to 192.168.1.100

Was this article helpful?

0 out of 0 liked this article

Still need help? Message Us